NACF.1000J1-S5/V Current Transducer
Applications
For the electronic measurement of currents: AC, DC,pulsed…, with galvanic separation between the primary circuits and the secondary circuits.
Advantages |
Applications |
Standards |
Small size and space savings |
Static converters |
EN 50178: 1997 |
Main electrical data (@±IPN, RL = 10 kΩ, CL=10000PF TA = 25℃) | |
Primary nominal current |
1000A |
Primary current measuring range |
±2500A |
Supply voltage |
DC±15(1±5%)V |
Current consumption |
≤±25mA |
Output voltage |
±4V |
Output internal resistance |
102Ω |
Load resistance |
≥10kΩ |
Accuracy - Dynamic performance data | |
Accuracy(excluding offset) |
≤±1%of IPN |
Linearity error |
≤±1%of IPN |
Electrical offset voltage |
≤±20mV |
Hysteresis offset voltage |
≤±30mV |
Temperature coefficient of δZt |
≤±1mV/℃ |
Temperature coefficient of VOUT |
≤±1mV/℃ |
Temperature coefficient of VOUT |
≤±1.5mV/℃ |
Step response time to 90 % of IPN |
≤5µS |
Frequency bandwidth (−3dB) |
DC … 25kHz |
General Data | |
Ambient operating temperature |
-40~+105℃ |
Ambient storage temperature |
-45~+105℃ |
Mass |
≤300g |
Insulation Coordination | |
Voltage for AC insulation test, 50Hz,1min |
5kV |
Isolation resistance |
≥1000MΩ |
Creepage distance |
9.9mm |
Clearance |
9.9mm |
NACF.1000J1-S5/V Dimensions NACF.1000J1-S5/V Series (in mm)
Connection
Mechanical Characteristics | |
General tolerance |
±1 mm |
Transducer fastening |
1 hole and 1 notch ø5.5mm |
Transducer fastening |
1 hole and 2 notches ø 4.5mm |
Recommended fastening torque |
2.5 N·m |
Primary through-hole |
40.5×30.5mm |
Connection of secondary |
Molex 22-04-1041 |
http://www.nb-csrsensor.com/